Rittal 7857.433 Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Alimentations sans interruption (UPS) Rittal 7857.433. Power - Hevacomp HELP! Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 9
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
UPS, single-phase, output range 1 – 12 kVA N+1 redundant
Power
795Rittal Catalogue 32/IT Solutions
B
5.4
Power
DK 7857.430, DK 7857.431,
DK 7857.432
Supply includes:
Single-phase UPS systems in
double-conversion technology
(VFI-SS 111) with internal “hot
swap” compatible batteries,
USB and serial interface.
DK 7857.433, DK 7857.434
Supply includes:
Single-phase UPS systems in
double-conversion technology
(VFI-SS 111), USB and serial
interface.
Available on request:
Replacement battery packs and
AS 400 interface adaptor.
UPS for 482.6 mm (19) racks or as floor-standing
enclosures
UPS with integral battery UPS control unit
Model No. DK 7857.430 7857.431 7857.432 7857.433 7857.434
Power
VA 1000 2000 3000 4500 6000
Watts 700 1400 2100 3150 4200
Max. heat loss (W) 105 210 252 315 420
Input
Rated voltage 230 V (160 – 288 V)
Frequency 50/60 Hz ±5 %
Power factor > 0.99 with linear load
Output
Voltage 230 V ±1 % (200/208/220/230/240 V adjustable)
Frequency, synchronised ± 1 Hz
Frequency, asynchronous ±0.1 % ±0.1 % ±0.1 % ±0.2 % ±0.2 %
Crest factor 3 : 1
Non-linear distortion 7 % 7 % 7 % 6 % 6 %
Wave shape 3 %
Operating ratio, AC mode 85 % 85 % 88 % 90 % 90 %
Operating ratio, battery mode 83 % 83 % 85 % 87 % 87 %
Power factor 0.7
Battery
5 years EUROBAT 5 years EUROBAT 5 years EUROBAT 5 years EUROBAT 5 years EUROBAT
Autonomy at 100 % load 7 min 7 min 5 min 12 min 8 min
Overload
105 % continuous
120 % 30 sec 30 sec 30 sec 160 sec 160 sec
150 % 10 sec 10 sec 10 sec 160 sec 160 sec
Communication
Interface 1 x USB, 1 x RS-232
SNMP Optional SNMP card DK 7857.420
Operating systems supported Windows, Unix, Linux, OS/2, Novell, Apple; RCCMD shutdown licence DK 7857.421
Emergency Power Off (EPO)
Mechanics
Width mm 440
Height mm 88
Depth mm 405 650 650 660 660
Weight kg 15.7 29.4 29.7 24 24
Input connection 230 V 10 A C14 10 A C20
Compact connector Compact connector
Output connection 230 V 6 x 10 A, C13, 2 units switched
4 x 10 A, C13,
2 units switched,
1 x 16 A, C19
Compact connector Compact connector
Operating
environment
Humidity 0 – 90 %, non-condensing
Noise level 50 db (A)
Safety IEC/EN 62 040-1, EN 60 950-1
Standards and
certifications
Power IEC/EN 62 040-3
EMC EN 50 091-2/EN 62 040-2 class A, EN 61 000-4-2/-3/-4/-6-8/-11, EN 61 000-3-2/-3
Labelling CE, FCC, cUL
<
< < < < <
<
> > > > >
The UPS is distinguished by
the use of double-conversion
technology.
Double-conversion technology
provides the basis for an opti-
mum supply voltage to all con-
nected loads. This means that
the Rittal PMC 12 UPS is ideallly
suited to all applications in the
IT environment, as well as for
all other requirements such as
medical technology, automation
technology, plant control etc.
A scalable autonomy of up to 2 h
at 100 % load ensures a broad
spectrum of applications.
Rittal Power Modular Concept
PMC 12
Double conversion technol-
ogy VFI-SS 111
For use as a rack or floor-
standing enclosure with 90°
rotating LCD display
2 U high
Serial/USB interface and
Emergency Power Off (EPO)
contact
Batteries “hot swap” compati-
ble, may be exchanged from
the front
Integral batteries with
1 – 3 kVA
External batteries with 4.5 kVA
and 6 kVA
Parallel switching 4.5 kVA and
6 kVA UPS up to 12 kVA N+1
redundant
Optional SNMP card
Also required:
Country-specific connection
cables and slide rails are
required to operate the UPS
systems.
For DK 7857.433, DK 7857.434
Parallel Hot Swap Chassis
(DK 7857.443 or DK 7857.444).
External 3 U battery pack
(DK 7857.442).
Vue de la page 0
1 2 3 4 5 6 7 8 9

Résumé du contenu

Page 1

UPS, single-phase, output range 1 – 12 kVA N+1 redundantPower795Rittal Catalogue 32/IT SolutionsB5.4PowerDK 7857.430, DK 7857.431, DK 7857.432Supply i

Page 2

PowerUPS, single-phase, output range 1 – 12 kVA N+1 redundant796 Rittal Catalogue 32/IT SolutionsB5.4PowerBlock diagram parallel redundant UPS DK 7857

Page 3

UPS, Rittal Modular Power Concept – PMC 200Power797Rittal Catalogue 32/IT SolutionsB5.4PowerThe new UPS generation: Rittal PMC 200 202020202020UPS rac

Page 4 - Energy saving

PowerUPS, Rittal Modular Power Concept – PMC 200798 Rittal Catalogue 32/IT SolutionsB5.4PowerN + 1 = Perfect redundancy in a rack with PMC 20040401212

Page 5

UPS, Rittal Modular Power Concept – PMC 200Power799Rittal Catalogue 32/IT SolutionsB5.4PowerSuper-fast service with PMC 200 20202020Extremely short MT

Page 6

PowerUPS, Rittal Modular Power Concept – PMC 200800 Rittal Catalogue 32/IT SolutionsB5.4PowerNote:This table contains only sample configurations. We w

Page 7 - Technical specifications

Technical specificationsPower801Rittal Catalogue 32/IT SolutionsB5.4Power1. Rectifier dataModule range up to 100 kW up to 200 kWModule types 101520253

Page 8 - Static Transfer Switch (STS)

PowerTechnical specifications802 Rittal Catalogue 32/IT SolutionsB5.4Power5. General technical specificationsModule range up to 100 kW up to 200 kWMod

Page 9 - Monitoring of UPS and

SoftwarePower803Rittal Catalogue 32/IT SolutionsB5.4PowerMonitoring of UPS and Static Transfer Switch (STS) This monitoring and management software ca